Beschreibung
● 8 Digital Outputs and 7 Digital Inputs
● Open Collector Output
● Non-isolated for all Channels
● Digital Input Channels Can Be Used As 16-bit Counters
● Configurable Power-on Value Settings
● Configurable Safe Value Settings
● Dual Watchdog
● Wide Operating Temperature Range: -25 ~ +75°C
Spezifikation
- Model
- I-7050A
- Digital Input/Counter
- Channels
- 7
- Type
- Dry Contact
- Sink
- Wet Contact
- Source
- Wet Contact
- On Voltage Level
- +4 ~ 30 VDC
- Off Voltage Level
- +1 VDC Max.
- Dry Contact
- On Voltage Level
- -
- Off Voltage Level
- -
- Effective Distance
- -
- for Dry Contact
- Counters
- Max. Count
- 65535 (16-bit)
- Max. Input
- 100 Hz
- Frequency
- Min. Pulse Width
- 5 ms
- Input Impedance
- 100 KΩ
- Channel-to-Channel Isolation
- -
- Overvoltage Protection
- -
- Digital Output
- Channels
- 8
- Type
- Open Collector
- Sink/Source (NPN/PNP)
- Source
- Overvoltage Protection
- +3.5 ~ 30 VDC
- Max. Load Current
- 50 mA/Channel
- Overvoltage Protection
- -
- Overload Protection
- -
- Power-on Value
- Yes
- Safe Value
- Yes
- Model
- I-7050A
- Communication
- Interface
- RS-485
- Bias Resistor
- No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.)
- Format
- (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
- Baud Rate
- 1200 ~ 115200 bps
- Protocol
- DCON (For I-7050 series)
- Modbus RTU, DCON (For M-7050 series)
- Dual Watchdog
- Yes, Module (1.6 Seconds), Communication (Programmable)
- LED Indicators/Display
- System LED Indicator
- Yes, 1 LED as Power/Communication Indicator
- I/O LED Indicators
- -
- 7-Segment LED Display
- -
- Isolation
- Intra-Module Isolation, Field-to-Logic
- -
- EMS Protection
- ESD (IEC 61000-4-2)
- -
- EFT (IEC 61000-4-4)
- -
- Surge (IEC 61000-4-5)
- -
- Power
- Reverse Polarity Protection
- Yes
- Input Range
- 10 ~ 30 VDC
- Consumption
- 0.5 W
- 0.4 W
- Mechanical
- Dimensions (W x L x H)
- 72 mm x 123 mm x 35 mm
- Installation
- DIN-Rail or Wall Mounting
- Environment
- Operating Temperature
- -25 ~ +75°C
- Storage Temperature
- -40 ~ +85°C
- Humidity
- 10 ~ 95% RH, Non-condensing
Filterkriterien
- Zollnummer
- 85176200
- Digital Out
- 08
- Digital In
- 07
- Eingabe Protokoll
- DCON
- Host-Schnittstelle
- Seriell
- Status
- Standard
- Hersteller
- ICPDAS