ASK US
Description

7-channel Relay Output Module

The I-7067 features 7-channel Form A power relay outputs. The I-7067D also has 7 LED indicators for power relay outputs. There are options for Power-on value and safe value for your consideration.

„● 7 Form A Power Relay
● Configurable Power-on Value Settings
● Configurable Safe Value Settings
● Dual Watchdog
„● Wide Operating Temperature Range: -25 ~ +75°C

Specification

Filter criteria

Customs Tariff Number
84718000
Digital Out
07
Protokoll
DCON
Status
Standard
Manufacturer
ICPDAS

Specification

Models
I-7067
I-7067D
Relay Output
Channels
7 (Form A)
Relay Type
Signal Relay
Form A Relay
Contact Rating
0.5 A @ 120 VAC
1 A @ 24 VDC
Min. Contact Load
1 mA @ 1 V
Contact Material
Gold overlay silver palladium
Operate Time
5 ms
Release Time
2 ms
Mechanical Endurance
5 × 106 ops.
Electrical Endurance
105 ops.
Surge Strength
1500 VDC
Power-on Value
Yes
Safe Value
Yes
Models
I-7067
I-7067D
Communication
Interface
RS-485
Format
(N, 8, 1), (N, 8, 2), (E, 8, 1), (O, 8, 1)
Baud Rate
1200 ~ 115200 bps
Protocol
DCON
Dual Watchdog
Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicator/Display
System LED Indicator
Yes, 1 LED as Power/Communication Indicator
I/O LED Indicators
-
Yes, 7 LEDs as Digital Input/Relay Output Indicators
7-Segment LED Display
-
Isolation
Intra-Module Isolation, Field-to-Logic
1500 VDC
EMS Protection
ESD (IEC 61000-4-2)
±4 kV Contact for each Terminal
±8 kV Air for Random Point
EFT (IEC 61000-4-4)
±2 kV for Power Line
Surge (IEC 61000-4-5)
-
Power
Reverse Polarity Protection
Yes
Input Range
10 ~ 30 VDC
Consumption
1.5 W
1.9 W
Mechanical
Dimensions (W x L x H)
72 mm x 123 mm x 35 mm
Installation
DIN-Rail or Wall Mounting
Environment
Operating Temperature
-25 ~ +75°C
Storage Temperature
-40 ~ +85°C
Humidity
10 ~ 95% RH, Non-condensing
Alternatives
Click here to opt-out of Google Analytics.